TECHNICAL DATABASE
Mitsubishi Heavy IndustriesKX/KXR/KXZ – VRF and subcodes
86 search entries, with any different interpretations for the same signal.
Not all subcodes belong to all generations. E30/E64 are specific KXZW; E36-3 KX6; E44 KXZ; E60 KX4/KX6.
Reference models
KX4 · KXR4 · KX6 · KXR6 · KXZ · KXZP · KXZR · KXZX · KXZRX · KXZW
| Code / indicator | Meaning | Documented aliases |
|---|---|---|
| E1 | Remote control communication–internal drive | — |
| E10 | Excessive number of internals on the same command | — |
| E11 | Master/slave directing of indoor units | — |
| E12 | Automatic and manual mixing methods | — |
| E16 | Anomalous indoor fan motor | — |
| E18 | Address or connection between internal master and slave | — |
| E19 | Improper operating/condensing pipe control mode | — |
| E2 | Address duplicated internal drive | — |
| E20 | Anomalous internal fan speed | — |
| E21 | Panel switch FDT faulty | — |
| E28 | Remote control temperature sensor | — |
| E3 | Outdoor unit signal line | — |
| E30 | Internal combination – non-compatible source unit (KXZW) | — |
| E31 | Address duplicated outdoor unit | — |
| E32 | Step L3 missing or incorrect phase sequence | — |
| E36 | Temperature sent or liquid return, second subcode | — |
| E36-1 | Temperature compressor 1, Tho-D1 | E36 1 |
| E36-2 | Temperature compressor 2, Tho-D2 | E36 2 |
| E36-3 | Liquid return (only KX6) | E36 3 |
| E37 | External heat exchanger/subcooler probes | — |
| E37-1 | External exchanger probe Tho-R1 | E37 1 |
| E37-2 | External exchanger probe Tho-R2 | E37 2 |
| E37-3 | External exchanger probe Tho-R3 | E37 3 |
| E37-4 | External exchanger probe Tho-R4 | E37 4 |
| E37-5 | Probe sottoraffreddatore1 Tho-SC | E37 5 |
| E37-6 | Probe sottoraffreddatore2 Tho-H | E37 6 |
| E38 | External air sensor Tho-A | — |
| E39 | Temperature probes sent compressors | — |
| E39-1 | Probe sent compressor 1 Tho-D1 | E39 1 |
| E39-2 | Probe sent compressor 2 Tho-D2 | E39 2 |
| E40 | High pressure: intervento63H1-1/2 | — |
| E41 | Overheating power transistors | — |
| E41-1 | Transistor power overheating CM1 | E41 1 |
| E41-2 | Transistor power overheating CM2 | E41 2 |
| E42 | Current compressor protection | — |
| E42-1 | Compressor current protection CM1 | E42 1 |
| E42-2 | Compressor current protection CM2 | E42 2 |
| E43 | Number or capacity of excessive interiors | — |
| E43-1 | Number of excessively connected indoor units | E43 1 |
| E43-2 | Excessive connected total capacity | E43 2 |
| E44 | Liquid return to the compressor (KXZ) | — |
| E44-1 | Compressor liquid return CM1 (KXZ) | E44 1 |
| E44-2 | Compressor liquid return CM2 (KXZ) | E44 2 |
| E45 | Inverter communication–external control board | — |
| E45-1 | Communication inverter1–external display | E45 1 |
| E45-2 | Communication inverter2–external display | E45 2 |
| E46 | Incompatible address methods in the same network | — |
| E48 | Outdoor fan motor DC abnormal | — |
| E48-1 | External fan FMO1 | E48 1 |
| E48-2 | External fan FMO2 | E48 2 |
| E49 | Too low intake pressure | — |
| E5 | Communication during operation | — |
| E51 | High Persistent Transistor Temperature | — |
| E51-1 | Persistent overheating transistor CM1 | E51 1 |
| E51-2 | Persistent overheating transistor CM2 | E51 2 |
| E53 | Compressor suction temperature sensor | — |
| E53-1 | Compressor suction sensor CM1 | E53 1 |
| E53-2 | Compressor suction sensor CM2 | E53 2 |
| E54 | Low or high pressure measurement, second subcode | — |
| E54-1 | Low-pressure sensor PSL | E54 1 |
| E54-2 | High-pressure sensor PSH | E54 2 |
| E55 | Temperature sensor under compressor cap | — |
| E55-1 | Sensor under compressor cap Tho-C1 | E55 1 |
| E55-2 | Sensor under compressor cap Tho-C2 | E55 2 |
| E56 | Power Transistor Temperature Sensor | — |
| E56-1 | Tho-P1 Transistor Power Sensor | E56 1 |
| E56-2 | Tho-P2 Transistor Power Sensor | E56 2 |
| E58 | Compressor outside synchronism | — |
| E58-1 | Loss synchronism compressor CM1 | E58 1 |
| E58-2 | Loss synchronism compressor CM2 | E58 2 |
| E59 | Launch of failed compressor | — |
| E59-1 | Missed compressor starter CM1 | E59 1 |
| E59-2 | Missed compressor starter CM2 | E59 2 |
| E6 | Internal exchange sensor | — |
| E60 | Compressor rotor position detection (KX4/KX6) | — |
| E60-1 | Compressor rotor position CM1 (KX4/KX6) | E60 1 |
| E60-2 | Compressor rotor position CM2 (KX4/KX6) | E60 2 |
| E61 | Communication between external master and slave | — |
| E61-1 | Communication with external slave1 | E61 1 |
| E61-2 | Communication with external slave2 | E61 2 |
| E63 | Emergency stop from CnT terminal | — |
| E64 | Water circulation/antifreeze protection of the source unit (KXZW) | — |
| E64-4 | Failure to consent water pump/antifreeze shutdown (KXZW) | E64 4 |
| E7 | Internal recovery air sensor | — |
| E75 | Communication of centralized control | — |
| E9 | Anomalous condensation discharge | — |
No entries match the filter.
Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.