TECHNICAL DATABASE

Mitsubishi ElectricMXZ-2A30/40/52VA – LEDs and fault memory

49 search entries, with any different interpretations for the same signal.

Reference models

MXZ-2A30VA · MXZ-2A40VA · MXZ-2A52VA

Code / indicatorMeaningDocumented aliases
LED1-1-LED2-ONFrequency limitation by current—
LED1-10-LED2-OFFSynchronism or compressor start—
LED1-13-LED2-OFFOutdoor fan—
LED1-2-LED2-OFFOvercurrent protection—
LED1-2-LED2-ONLimitation by temperature/pressure—
LED1-3-LED2-OFFHigh discharge temperature—
LED1-3-LED2-ONLimitation by sending temperature—
LED1-4-LED2-OFFHeat sink or board overheating—
LED1-4-LED2-ONTemperature too low—
LED1-5-LED2-OFFHigh pressure protection—
LED1-5-LED2-ONLimitation by temperature/pressure—
LED1-8-LED2-OFFCurrent detection—
LED1-9-LED2-OFFBus voltage DC—
LED1-9-LED2-ONTest mode or service—
LED1-ON-LED2-1Indoor unit and expansion valve—
LED1-ON-LED2-11Closed service valve—
LED1-ON-LED2-2Outdoor-unit power system—
LED1-ON-LED2-3Discharge temperature sensor—
LED1-ON-LED2-4Heat sink temperature sensor—
LED1-ON-LED2-5External air supply—
LED1-ON-LED2-7Memory or outdoor-unit control—
LED1-ON-LED2-ONNormal Indication—
MEM-10Temperature too low—
MEM-11Current detection—
MEM-14Power module—
MEM-15Indoor unit and expansion valve—
MEM-2Outdoor-unit power system—
MEM-3External heaters—
MEM-4Overcurrent protection—
MEM-5High discharge temperature—
MEM-6High pressure protection—
MEM-7Heat sink or board overheating—
MEM-8Outdoor fan—
MEM-9Memory or outdoor-unit control—
MEM-EST-LED1-1-LED2-OFFOvercurrent protection—
MEM-EST-LED1-2-LED2-OFFSynchronism or compressor start—
MEM-EST-LED1-3-LED2-OFFHeat sink or board overheating—
MEM-EST-LED1-4-LED2-OFFHeat sink or board overheating—
MEM-EST-LED1-6-LED2-OFFBus voltage DC—
MEM-EST-LED1-7-LED2-OFFPower module—
MEM-EST-LED1-8-LED2-OFFCurrent detection—
MEM-EST-LED1-9-LED2-OFFSynchronism or compressor start—
MEM-EST-LED1-ON-LED2-1Probe debriefing—
MEM-EST-LED1-ON-LED2-12Closed service valve—
MEM-EST-LED1-ON-LED2-2External air supply—
MEM-EST-LED1-ON-LED2-3Heat sink temperature sensor—
MEM-EST-LED1-ON-LED2-4Supplies temperature board—
MEM-EST-LED1-ON-LED2-5Memory or outdoor-unit control—
MEM-EST-LED1-ON-LED2-9External exchange probe—

Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.