TECHNICAL DATABASE

PanasonicThree-pipe ECOi – 2020 diagnostic table

74 search entries, with any different interpretations for the same signal.

Table for ECOi with three tubes. It is not a universal table for Sanyo, Argo or Airwell.

Code / indicatorMeaningDocumented aliases
E01Missed remote control serial reception—
E02Serial transmission of anomaly remote control—
E03Signal from remote or centralized abnormal control—
E04Anomalous indoor unit serial reception—
E06Main exterior: no reception from the interior—
E08Address of duplicated indoor unit—
E09Duplicate main remote command address—
E12Automatic directing already in progress on other line—
E15Indoor units detected less numerous than expected—
E16Larger indoor units than expected—
E18Main interior: non-receiving from secondary—
E20No internal detected during addressing—
E24Anomalous signal from external secondary to the main—
E25Address of wrong outdoor units—
E26Number of outdoor units other than the setting—
E27Harness between main and secondary erroneous—
E29Secondary external: no reception from the main—
E30Serial transmission of the abnormal outdoor unit—
E31Communication with abnormal MDC—
F01Internal battery probe E1—
F02Internal battery probe E2—
F03Internal battery probe E3—
F04Probe of compressor 1 DISCH1—
F05Probe of compressor 2 DISCH2—
F06External gas exchanger probe 1 EXG1—
F07External exchanger liquid probe 1 EXL1—
F08Outdoor air sensor TO—
F10Indoor return air sensor TA—
F11Indoor supply air sensor BL—
F12Compressor suction temperature sensor SCT—
F14Double-pipe heat exchanger gas outlet sensor SCG—
F16High pressure or high pressure alarm sensor—
F17Low pressure sensor—
F23External gas exchanger probe 2 EXG2—
F24External exchanger liquid probe 2 EXL2—
F29Memory EEPROM of the internal board—
F31Memory EEPROM main or secondary external—
H01Overcurrent compressor 1—
H03Compressor current 1 not detected when started—
H05Probe 1 unconnected compressor—
H06Low pressure pressure pressure pressure switch—
H08Compressor oil sensor 1—
H11Overcurrent compressor 2—
H12Compressor block 2 detected by current—
H13Compressor 2 current sensor CT: open or short circuit—
H15Probe 2 unconnected compressor—
H27Compressor oil sensor 2—
H31Protection IPM for current or temperature—
L02Matching the type of indoor unit not allowed—
L03Main address duplicated in the group—
L04Duplicated external system address—
L05Priority of duplicated indoor units—
L06Priority between non-priority and external interior—
L07Group cabling on internal with individual control—
L08Internal drive address not set—
L09Internal capacity code not set—
L10External capacity code not set—
L11Group cabling with mistaken shared electrovalve kit—
L17Outdoor units with different refrigerants combined—
P01Intervention thermal protection indoor fan—
P02Thermal protection compressor or abnormal power supply—
P03Compressor temperature 1 anomalous—
P04High pressure pressure pressure pressure switch—
P05Anomalous phase sequence—
P09Connection of the wrong ceiling panel—
P10Floating condensing switch—
P11Anomalous or blocked condensate discharge pump—
P12Internal fan inverter protection—
P14Low Oxygen Sensor Intervention—
P16Overcurrent detected by the DCCT—
P17Compressor temperature 2 anomalous—
P22Anomaly external fan—
P29Anomaly inverter compressor—
P31Alarm lock for other unit of the group—

Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.