E48Outdoor fan DC anomaly
PAC FDC/FDCA – R410A/R32 (Handbook2024)
This information applies to the specified product family. Confirm the full model and manual revision.
Documented models
FDT · FDTC · FDU · FDUA · FDUM · FDE · FDEN · FDC VN/VNA/VNP/VNX/VNXA/VS/VSA/VSX · FDCA
What it means
Outdoor fan DC abnormal. The required ventilation is not confirmed by the control. A lack of air flow can also cause secondary protection.
Possible causes to distinguish
- Fixed motor or with uneven rotation, faulty wiring or loose connector.
- Control circuit or match turns to check.
What to tell the repair lab
Record the full code and photograph the display and the nameplates of the indoor and outdoor units. Tell the laboratory when the shutdown occurs and whether it affects one or more units; avoid repeated restarts.
Technical guidance
Guidance for qualified personnel, to be checked against the unit’s service manual.
- With the unit disconnected from its power supply, check for mechanical obstructions.
- The technician separates motor control from power supply and feedback on the board.
Table PAC with external FDC/FDCA. For systems with external RAC/SRC use the dedicated table of the relevant manual.
Does this necessarily mean the board is faulty?
The code indicates a condition detected by the control. Before evaluating the electronic repair, it is necessary to distinguish the circuit concerned, the connections and operating conditions. Model and description of the defect allow the repair lab to evaluate the case.
Source for this interpretation: Mitsubishi Heavy Industries Service Support Handbook, revisione 18/06/2024 r9 · page 14 (PDF15).
Contact the repair labThe brand, series and code are already in the message