OPER-6 / OPERATION-6External temperature sensor
SLZ-A09/12/18AR – Operation indicator flashes
OPER-n indicates no flashes of the Operation lamp, not an alphanumeric code of the manufacturer. The count identifies the table fault group.
Documented models
SLZ-A09AR · SLZ-A12AR · SLZ-A18AR · SLZ-A09AR.TH · SLZ-A12AR.TH · SLZ-A18AR.TH
Indicator light pattern · search label, not an alphanumeric display code
Indicator: Operation. Flashes: 6.
What it means
Six flashes indicate anomaly of the external thermostore or its wiring/circuit on the inverter board.
Possible causes to distinguish
- Open-circuit or short-circuited sensor, intermittent connection, or incorrectly installed sensor.
- Check the board’s input circuit after checking the sensor and wiring.
What to tell the repair lab
Photograph the fault indication and nameplate and tell the laboratory when the shutdown occurs. Do not open electrical compartments or make repeated restart attempts.
Technical guidance
Guidance for qualified personnel, to be checked against the unit’s service manual.
- Identify the affected sensor and compare its measured value with the characteristic curve in the manual.
- Check the connector and wiring before concluding that the board is faulty.
Count lamp flashes Operation. Key OPER-6 is a site notation, not an alphanumeric code of the manufacturer.
Does this necessarily mean the board is faulty?
The code indicates a condition detected by the control. Before evaluating the electronic repair, it is necessary to distinguish the circuit concerned, the connections and operating conditions. Model and description of the defect allow the repair lab to evaluate the case.
Source for this interpretation: Mitsubishi Electric SLZ-A09/12/18AR – Technical & Service Manual OC302 · page 10.