4250 / U6Power module fault
City Multi PUMY-P200YKM2
This information applies to the specified product family. Confirm the full model and manual revision.
Documented models
PUMY-P200YKM2 · PUMY-P200YKM2R1 · PUMY-P200YKM2R2 · PUMY-P200YKM2-BS · PUMY-P200YKM2R1-BS · PUMY-P200YKM2-ETR2 · PUMY-P200YKM2-ERR2 · PUMY-P200YKM2-BSR2 · PUMY-P200YKM2-ETBSR2 · PUMY-P200YKM2-ERBSR2
What it means
The protection indication concerns the inverter circuit that powers the compressor. Code U6 corresponds to 4250 in this product family: it does not, by itself, prove that the circuit board needs replacement.
Possible causes to distinguish
- Short circuit or faulty connection to the compressor
- Electrical fault in the compressor
- Faulty power module or inverter circuit
What to tell the repair lab
Photograph the fault indication and the nameplate. Tell the laboratory when the shutdown occurs and whether it recurs. Checks on circuit boards, wiring and the refrigerant circuit require a qualified technician.
Technical guidance
Guidance for qualified personnel, to be checked against the unit’s service manual.
- Check the compressor connections, its electrical integrity and the power circuit according to the manual; assess the circuit board after ruling out the external loads as the cause.
Does this necessarily mean the board is faulty?
The code indicates a condition detected by the control. Before evaluating the electronic repair, it is necessary to distinguish the circuit concerned, the connections and operating conditions. Model and description of the defect allow the repair lab to evaluate the case.
Source for this interpretation: Mitsubishi Electric OCH675E – PUMY-P200YKM2, revisione E (2020) · page 65.