TECHNICAL DATABASE

LGMulti V 5 ARUM – full outdoor-unit display code

162 search entries, with any different interpretations for the same signal.

Insert the entire number of the external display. The final digit indicates normalmente1=master,2=slave1,3=slave2. Exceptions documentate511/512: two different capacity errors. A logical code CH242 is distinguished from display242 (CH24 out of slave1).

Reference models

ARUM072BTE5 · ARUM072DTE5 · ARUM096BTE5 · ARUM096DTE5 · ARUM121BTE5 · ARUM121DTE5 · ARUM144BTE5 · ARUM144DTE5 · ARUM168BTE5 · ARUM168DTE5 · ARUM192BTE5 · ARUM192DTE5 · ARUM216BTE5 · ARUM216DTE5 · ARUM241BTE5 · ARUM241DTE5

Code / indicatorMeaningDocumented aliases
1041Communication between outdoor units master and slave – external master—
1042Communication between outdoor units master and slave – external slave1—
1043Communication between outdoor units master and slave – external slave2—
1051Communication board fans–inverter compressor – external master—
1052Communication fan board–inverter compressor – external slave1—
1053Communication fan board–inverter compressor – external slave2—
1061IPM outdoor fan protection – external master—
1062Protection IPM outdoor fan – exterior slave1—
1063Protection IPM outdoor fan – exterior slave2—
1071Insufficient Voltage DC Fan Inverter – External Master—
1072Voltage DC insufficient fan inverter – external slave1—
1073Voltage DC insufficient fan inverter – external slave2—
1131Liquid pipe temperature sensor – external master—
1132Liquid pipe temperature sensor – external slave1—
1133Liquid pipe temperature sensor – external slave2—
1141Subcooler input sensor – external master—
1142Subcooler input sensor – external slave1—
1143Subcooler input sensor – external slave2—
1151Subcooler output sensor – external master—
1152Subcooler output sensor – external slave1—
1153Subcooler output sensor – external slave2—
1161Insufficient oil level or abnormal oil level sensor – external master—
1162Insufficient oil level or abnormal oil level sensor – external slave1—
1163Insufficient oil level or abnormal oil level sensor – external slave2—
1451Communication main board–additional external board – external master—
1452Communication main board–additional external board – external slave1—
1453Communication main board–additional external board – external slave2—
1501Insufficient delivery superheat and liquid return risk – external master—
1502Insufficient superheat and liquid return risk – external slave1—
1503Insufficient superheat and liquid return risk – external slave2—
1511Difference between high and low insufficient pressure – external master—
1512Difference between high and low insufficient pressure – external slave1—
1513Difference between high and low insufficient pressure – external slave2—
1531Upper external heat exchanger sensor – external master—
1532External temperature sensor - external slave1—
1533External temperature sensor - external slave2—
1541Lower external heat exchanger sensor – external master—
1542External temperature sensor inferior – external slave1—
1543External temperature sensor inferior – external slave2—
1821Main/secondary microcontroller communication of the additional board – external master—
1822Main/secondary microcontroller communication of the additional board – external slave1—
1823Main/secondary microcontroller communication of the additional board – external slave2—
1871Hydro Kit antifreeze protection – external master—
1872Hydro Kit antifreeze protection – external slave1—
1873Hydro Kit antifreeze protection – external slave2—
1931Blower inverter heatsink – external master—
1932Blower inverter heatsink – external slave1—
1933Blower inverter heatsink – external slave2—
1941Fan heat dissipator sensor – external master—
1942Fan heat dissipator sensor – external slave1—
1943Fan heat dissipator sensor – external slave2—
2001Automatic search for unfinished pipes – display2001—
211Protection IPM compressor inverter for overcurrent phase – external master—
212Protection IPM compressor inverter for phase overcurrent – external slave1—
213Protection IPM compressor inverter for phase overcurrent – external slave2—
221Overcurrent input AC of the inverter board – external master—
222Overcurrent input AC of the inverter board – external slave1—
223Overcurrent input AC of the inverter board – external slave2—
231Anomalous voltage on the connection DC of the inverter compressor – external master—
232Anomalous voltage on the connection DC of the inverter compressor – external slave1—
233Anomalous voltage on the connection DC of the inverter compressor – external slave2—
241High pressure switch of outdoor unit – external master—
242High pressure switch of the outdoor unit – external slave1—
2421Centralized control network communication – external master—
2422Centralized control network communication – external slave1—
2423Centralized control network communication – external slave2—
243High pressure switch of the outdoor unit – external slave2—
251External power voltage too high or too low – external master—
252External power voltage too high or too low – external slave1—
253External power voltage too high or too low – external slave2—
261Missed start of the inverter compressor – external master—
262Missed start of the inverter compressor – external slave1—
263Missed start of the inverter compressor – external slave2—
291Overcurrent inverter compressor – external master—
292Overcurrent inverter compressor – external slave1—
293Overcurrent inverter compressor – external slave2—
321Excessive compressor temperature inverter1 – external master—
322Compressor temperature inverter1 excessive – external slave1—
323Compressor temperature inverter1 excessive – external slave2—
331Excessive compressor temperature inverter2 – external master—
332Compressor temperature inverter2 excessive – external slave1—
333Compressor temperature inverter2 excessive – external slave2—
341High pressure protection detected by control – external master—
342High pressure protection detected by the control – external slave1—
343High pressure protection detected by the control – external slave2—
351Intake pressure lower than operating limit – external master—
352Intake pressure lower than operating limit – external slave1—
353Intake pressure lower than operating limit – external slave2—
361Insufficient compression ratio – external master—
362Insufficient compression ratio – external slave1—
363Insufficient compression ratio – external slave2—
401Inverter compressor current sensor CT – outdoor unit master—
402Inverter compressor current sensor CT – outdoor unit slave1—
403Inverter compressor current sensor CT – outdoor unit slave2—
411Temperature sensor sent compressor 1 – external master—
412Temperature sensor sent compressor 1 – external slave1—
413Temperature sensor sent compressor 1 – external slave2—
421Low pressure transducer – external master—
422Low pressure transducer – external slave1—
423Low pressure transducer – external slave2—
431High pressure transducer – external master—
432High pressure transducer – external slave1—
433High pressure transducer – external slave2—
441External air temperature sensor – external master—
442External air temperature sensor – external slave1—
443External air temperature sensor – external slave2—
451External temperature sensor – external master—
452External temperature sensor – external slave1—
453External temperature sensor – external slave2—
461Intake temperature sensor – external master—
462Suction temperature sensor – external slave1—
463Suction temperature sensor – external slave2—
471Temperature sensor sent compressor 2 – external master—
472Temperature sensor sent compressor 2 – external slave1—
473Temperature sensor sent compressor 2 – external slave2—
491Temperature sensor IPM – external master—
492Temperature sensor IPM – external slave1—
493Temperature sensor IPM – external slave2—
501Power phase of the missing outdoor unit – external master—
502Power phase of the missing outdoor unit – external slave1—
503Power phase of the missing outdoor unit – external slave2—
511Internal/external capacity ratio—
512Excessive capacity on recuperator/retrieval time—
521Communication main board–inverter of outdoor unit – external master—
522Communication main board–inverter of outdoor unit – external slave1—
523Communication main board–inverter of outdoor unit – external slave2—
531Outdoor unit communication – indoor unit – external master—
532Outdoor unit communication – indoor unit – external slave1—
533Outdoor unit communication – indoor unit – external slave2—
571Inverter does not receive data from the main board – external master—
572Inverter does not receive data from the main board – external slave1—
573Inverter does not receive data from the main board – external slave2—
601EEPROM outdoor inverter board – external master—
602EEPROM outdoor inverter board – external slave1—
603EEPROM of external inverter board – external slave2—
621High temperature of the compressor inverter heatsink – external master—
622High temperature of the compressor inverter heatsink – external slave1—
623High temperature of the compressor inverter heatsink – external slave2—
651Sensor temperature heatsink inverter – external master—
652Sensor temperature heatsink inverter – external slave1—
653Sensor temperature heatsink inverter – external slave2—
671External fan blocked – external master—
672External fan blocked – external slave1—
673External fan blocked – external slave2—
711Outdoor inverter current sensor CT – outdoor unit master—
712Outdoor inverter current sensor CT – outdoor unit slave1—
713Outdoor inverter current sensor CT – outdoor unit slave2—
751Outdoor fan current sensor CT – outdoor unit master—
752Outdoor fan current sensor CT – outdoor unit slave1—
753Outdoor fan current sensor CT – outdoor unit slave2—
771External fan overcurrent – external master—
772External fan overcurrent – external slave1—
773External fan overcurrent – external slave2—
791Lack initial determination of fan position – external master—
792Lack initial determination of fan position – external slave1—
793Lack initial determination of fan position – external slave2—
861EEPROM of external main board – external master—
862EEPROM external main board – external slave1—
863EEPROM external main board – external slave2—
871EEPROM outdoor fan board – external master—
872EEPROM outdoor fan board – external slave1—
873EEPROM outdoor fan board – external slave2—

Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.