TECHNICAL DATABASE
DaikinVRV X RXQ
61 search entries, with any different interpretations for the same signal.
Guidance table retained from the previous release: check the full model and subcode. It does not cover every historical unit.
| Code / indicator | Meaning | Documented aliases |
|---|---|---|
| A0 | Anomaly external protection device (indoor unit) | — |
| A1 | Anomaly PCB indoor unit | — |
| A3 | Anomalous drainage level control system | — |
| A6 | Lock, overload or anomaly internal fan motor | — |
| A8 | Anomaly supply voltage | — |
| A9 | Anomaly coil electronic expansion valve or obstruction | — |
| AF | Anomalous humidifying system | — |
| AH | Automatic Grid Unit Error | — |
| AJ | Anomaly device determination capacity | — |
| C1 | Anomaly transmission between PCB indoor units and PCB fan / grill | — |
| C4 | Anomaly termistore liquid tube internal heat exchanger | — |
| C5 | Anomaly termistore gas tube internal heat exchanger | — |
| C6 | Anomalous combination PCB internal/PCB fan or capacity setting | — |
| C9 | Anomalous indoor air vacuum cleaner | — |
| CE | Sensor failure / infrared floor | — |
| CJ | Remote control thermal anomalous | — |
| E1 | Anomaly PCB main outdoor unit | — |
| E2 | Electrical Dispersion Detection or missing detection core | — |
| E3 | High pressure pressure pressure pressure switch | — |
| E4 | Low Pressure Sensor Intervention | — |
| E5 | Inverter compressor motor block | — |
| E7 | Anomaly external fan motor | — |
| E9 | Anomaly coil external electronic expansion valve | — |
| F3 | Anomaly temperature mandata tube | — |
| F4 | Alarm wet | — |
| F6 | Refrigerant overload | — |
| H3 | Anomalous wiring between PCB main external and PCB inverter | — |
| H7 | Anomaly PCB outdoor fan | — |
| H9 | Anomalous external air temperature | — |
| J3 | Anomaly termistore mandata tube / compressor body | — |
| J5 | Anomaly termistore suction tube | — |
| J7 | Anomaly termistore liquid tube heat exchanger | — |
| J8 | Anomaly termistore liquid tube exchanger | — |
| J9 | Anomaly termistore gas tube heat exchanger | — |
| JA | Anomalous high pressure sensor | — |
| JC | Low pressure sensor | — |
| L1 | Anomaly PCB inverter | — |
| L2 | Interruption momentary power supply during operational testing | — |
| L4 | Anomalous temperature dissipator inverter | — |
| L5 | Overcurrent instant compressor | — |
| L8 | Overcurrent compressor | — |
| L9 | Anomaly start compressor | — |
| LC | Error transmission between PCB inverter and PCB main outdoor unit | — |
| P1 | Squilibrium Voltage Supply | — |
| P3 | Anomaly reactor temperature | — |
| P4 | Anomaly temperature dissipator inverter | — |
| PJ | Anomalous capacity setting / combination PCB after replacement PCB main external | — |
| U0 | Refrigerant deficiency notice | — |
| U1 | Lack of phase / reverse phase according to expected control | — |
| U2 | Insufficient power supply or instant anomaly | — |
| U3 | Operating test not performed | — |
| U4 | Transmission error between indoor and outdoor units | — |
| U5 | Remote command and internal drive transmission error | — |
| U7 | Transmission error between outdoor units | — |
| U8 | Communication error between main and secondary remote commands | — |
| U9 | Anomaly of other internal/external systems | — |
| UA | Uncorrect combination between internal, external or remote control units | — |
| UC | Central control address duplication | — |
| UE | Transmission error between centralized control and indoor unit | — |
| UF | System not yet configured | — |
| UH | Anomalous system / address of undefined refrigerant circuit | — |
No entries match the filter.
Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.